GEM 1242 Operating Instructions Manual page 28

Electrical position indicator
Hide thumbs Also See for 1242:
Table of Contents

Advertisement

13 Specific data – IO-Link
Feedback
(threshold)
CLOSED
Total stroke
Stroke reduction
OFF
Stroke reduction
25 %
Stroke reduction
50 %
Stroke reduction
75 %
Feedback
(threshold)
The setting is a percentage of the set switch point tolerance (threshold).
Off
25%
50%
75%
The delay time before the warning occurs corresponds to the time of the parameter Alarm opening time.
▶ If the parameter Alarm opening time is deactivated (setting 0), the alarm Stroke reduction is deactivated.
Alarm stroke reduction closed
Corresponds to Alarm stroke reduction open but for CLOSED position.
The delay time before the warning occurs corresponds to the time of the parameter Alarm closing time.
▶ If the parameter Alarm closing time is deactivated (setting 0), the alarm Stroke reduction is deactivated.
Programmed position open
AD value of the OPEN position of the last correctly executed end position programming.
Programmed position closed
AD value of the CLOSED position of the last correctly executed end position programming.
Programmed stroke
Determined stroke of the linear actuator during the last correctly executed end position programming (in AD values). The
change in valve stroke can be calculated in conjunction with the parameter "Last stroke".
GEMÜ 1242
Feedback
(threshold)
OPEN
Feedback
(threshold)
Setting
Warning deactivated
Warning becomes active 25% before loss of end position feed-
back
Warning becomes active 50% before loss of end position feed-
back
Warning becomes active 75% before loss of end position feed-
back
NOTICE
NOTICE
28 / 41
Function
www.gemu-group.com