Table of Contents

Advertisement

Diagnostics

Table 5.
Diagnostics: LED1, LED2, LED3 on the sensor
User action
LED display
Press Test
LED1: Off
button (S5)
LED2: Off
LED3: 1-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3: 2-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3: 4-blink pattern repeated 3 times
i
Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
Table 6.
Diagnostics: LED1, LED2, LED3 on the receiver
User action
LED display
None
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3: 2-blink pattern repeated continuously
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated 3 times
i
Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
BAS-SVX04A-EN • Wireless Zone Sensor
Operation, Maintenance, and Troubleshooting
LED1, LED2, and LED3 will respond to diagnostics by exhibiting specific blinking
patterns. They will occur on the sensor as a result of pressing the Test button (S5)
(Table
5). They will occur on the receiver independently of any user action
(Table
6).
i
i
Indicates...
Disassociated
• Sensor is not associated with a receiver.
Address set to 000
• Address not set to between 001–999.
Not configured
• Sensor configuration properties not properly set
(defective sensor).
Input voltage too high
• No RF transmission is permitted with an input battery
voltage greater than 3.9 V.
Indicates...
Disassociated
• Receiver is not associated, waiting for a sensor.
• Receiver lost communication with sensor.
• Receiver has no devices on its wireless personal area
network.
• Association with a device has been manually removed.
Address set to 000
• Address not set to between 001–999.
Not configured
• Receiver configuration properties not properly set
(defective receiver).
33