06-10
Over-torque Detection Time (OT2)
Control
VF
VFPG
mode
Settings
Pr.06-05 and Pr.06-08 determine the operation mode of the drive after the over-torque is
detected via the following method: if the output current exceeds the over-torque detection level
(Pr.06-06) and also exceeds the Pr.06-07 Over-Torque Detection Time, the fault code
"OT1/OT2" is displayed. If a Multi-Functional Output Terminal is to over-torque detection, the
output is on. Please refer to Pr.02-11~02-22 for details.
06-11
Current Limit
Control
FOCPG TQCPG
mode
Settings
It is used to set the current limit.
06-12
Electronic Thermal Relay Selection
Control
VF
VFPG
mode
Settings
It is used to prevent self-cooled motor overheats under low speed. User can use electrical
thermal relay to limit driver's output power.
06-13
Electronic Thermal Characteristic
Control
VF
VFPG
mode
Settings
Revision Nov. 2008, VLE1, SW V1.03
SVC
FOCPG TQCPG FOCPM
0.0 to 60.0 sec
current
Pr.06-07, 06-10
0 to 250%
SVC
FOCPG TQCPG FOCPM
0
Inverter motor
1
Standard motor
2
Disabled
SVC
FOCPG TQCPG FOCPM
30.0 to 600.0 sec
Chapter 4 Parameters|
Factory setting: 0.1
5%
Pr.06-06,
Pr.06-09
Factory setting: 150
Factory setting: 2
Factory setting: 60.0
Unit: 0.1
Unit: 1
Unit: 0.1
4-65