Viessmann Vitodens 333 Service Instructions Manual page 89

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Repairs
(cont.)
Coding
Coding in the delivered condition
Burner
7d:0
Air factor correction 0
82:0
Operation with natural
gas
83:15
Ignition start gas vo-
lume 15%
84:0
Start capacity correc-
tion 0%
85:0
Standard mode
Possible change
7d: 5
Note
to
A change is only possible
7d:10
if manual calibration was
first carried out via cod-
ing address "85".
Air factor correction ad-
justable from
Each step represents an
air factor modification of
approx. 0.01.
82:1
Operation with LPG
83:0
Start gas volume adjusta-
to
ble from 0 to 31%
83:31
84: 8
Start capacity correction
to
adjustable from 16 to
84:7
+14%.
One step equals 2%.
85:1
Manual calibration of the
combustion control unit.
The red fault indicator
also flashes during cali-
bration. The process has
terminated when the red
indicator no longer
flashes (after approx. 1
min). The air factor can
then be manually altered
in coding address "7d".
Note
Heat must be drawn off
during manual calibra-
tion.
Troubleshooting
5 to 10.
89