Viessmann Vitodens 333 Service Instructions Manual page 78

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Display
Const.
Weath.
fault
comp.
code
Ed
X
X
F0
X
X
F1
X
X
F2
X
X
F3
X
X
F4
X
X
F8
X
X
78
System char-
Cause
acteristics
Burner control
Internal fault
unit fault
Burner
Internal fault
blocked
Burner control
Flue gas
unit fault
temperature
limiter has
responded
Burner control
The tem-
unit fault
perature lim-
iter has
responded
Burner control
Flame signal
unit fault
is already
present at
burner start
Burner control
No flame sig-
unit fault
nal
Burner control
The fuel
unit fault
valve closes
too late
Remedy
Replace the con-
trol unit
Replace the con-
trol unit
Check flue gas
path/route; press
"E"
Check the heating
system fill level,
the circulation
pump, the tem-
perature limiter
and interconnect-
ing cables/leads;
vent the system;
press "E"
Check the ionisa-
tion electrode and
interconnecting
leads; press "E"
Check the ionisa-
tion electrode,
ignition, ignition
module, intercon-
necting cables
and leads, gas
pressure, gas
combination valve
and the ionisation
current; press
"E"
Check the gas
combination valve
and both control
paths; press "E"