Function description
Control functions
Reducing the heat up time
During the transition from operation
with reduced room temperature to
operation with standard room tem-
perature, the boiler water or flow tem-
perature will be raised in accordance
with the selected heating curve. The
boiler water or flow temperature can
be automatically increased.
Example using the settings in the delivered condition
A Start of operation with standard
room temperature
B Set boiler water or flow tempera-
ture in accordance with the
selected heating curve
104
(cont.)
The value and duration of the addi-
tional increase of the set boiler water
temperature or flow temperature can
be adjusted in the coding addresses
"FA" and "Fb".
C Set boiler water or flow tempera-
D Duration of operation with raised
ture in accordance with coding
address "FA":
50 °C + 20 % = 60 °C
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min