Fault codes
(cont.)
Display
Const.
Weath.
fault
comp.
code
30
X
X
38
X
X
40
X
48
X
50
X
X
51
X
X
58
X
X
59
X
X
A7
X
System char-
Cause
acteristics
Burner
Boiler water
blocked
temperature
sensor
shorted out
Burner
Boiler water
blocked
temperature
sensor lead
broken
Mixer closes
Mixer circuit
M2 flow tem-
perature
sensor
shorted out
Mixer closes
Mixer circuit
M2 flow tem-
perature
sensor lead
broken
No DHW heat-
Cylinder pri-
ing
mary tem-
perature
sensor
shorted out
No DHW heat-
Outlet tem-
ing
perature
sensor
shorted out
No DHW heat-
Cylinder pri-
ing
mary tem-
perature
sensor lead
broken
No DHW heat-
Outlet tem-
ing
perature
sensor lead
broken
Control mode
Faulty pro-
as per the de-
gramming
livered condi-
unit
tion
Troubleshooting
Remedy
Check the boiler
water tempera-
ture sensor (see
page 81)
Check the boiler
water tempera-
ture sensor (see
page 81)
Check the flow
temperature sen-
sor
Check the flow
temperature sen-
sor
Check sensors
(see page 81)
Check sensors
(see page 81)
Check sensors
(see page 81)
Check sensors
(see page 81)
Replace the pro-
gramming unit
73