Code 2
(cont.)
Coding in the delivered condition
7F:1
Detached house (only
for weather compen-
sated control units)
80:1
A fault message is dis-
played, providing a fault
is active for at least 5 s
81:1
Automatic summer/win-
ter time changeover
82:0
Operation with natural
gas
88:0
Temperature displayed
in °C (Celsius)
8A:175
Do not adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature 21.3 h
Possible change
7F:0
Apartment block
Separate adjustment for
holiday program and time
program for DHW heat-
ing, as option
80:0
Immediate fault message
80:2
The fault message is is-
to
sued after a delay, which
80:199
is adjustable from 10 s to
995 s; 1 step = 5 s
81:0
Manual summer/winter
time changeover
81:2
Use of the radio clock re-
ceiver (automatic recog-
nition)
81:3
With LON communication
module: The control unit
receives the time
82:1
Operation with LPG (only
adjustable if coding ad-
dress 11:9 has been set;
see page 88)
88:1
Temperature displayed in
°F (Fahrenheit)
90:1
Fast (low values) or slow
to
(high values) matching of
90:199
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min