Viessmann Vitodens 333 Service Instructions Manual page 16

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps
16
(cont.)
1. Close the gas shut off valve.
2. Release screw A inside test nipple
"PE" on the gas combination valve,
but do not remove it; then connect
the pressure gauge.
3. Open the gas shut off valve.
4. Measure the static pressure and
record it in the service report on
page 118.
Set value: max. 57.5 mbar.
5. Start the boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 s, press "E" to reset the
burner.
6. Check the supply (flow) pressure.
Set values:
Natural gas 20 mbar
LPG 50 mbar
Note
Use suitable test equipment with a
resolution of at least 0.1 mbar, to
measure the supply pressure.
7. Record the actual value in the ser-
vice report.
Take the action shown in the table.