Viessmann Vitodens 333 Service Instructions Manual page 57

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Code 2
(cont.)
Parameter ad-
With heating circuit pump logic function:
dress b5:...
Heating circuit pump "OFF"
1
RT
actual
2
RT
actual
3
RT
actual
4
RT
actual
5
RT
actual
6
RT
actual
7
RT
actual
8
RT
actual
Coding in the delivered condition
Heating circuit A1/M2
C5:20
Electronic minimum
flow temperature limit
20 °C (only for weather
compensated control
units)
C6:74
Electronic maximum
flow temperature limit
74 °C (only for weather
compensated control
units)
d3:14
Heating curve slope =
1.4 (only for weather
compensated control
units)
d4:0
Heating curve slope = 0
(only for weather com-
pensated control units)
d5:0
The external heating
program changeover al-
ters the heating pro-
gram to "Constant
operation with reduced
room temperature"
(only for weather com-
pensated control units)
> RT
+ 5 K
set
> RT
+ 4 K
set
> RT
+ 3 K
set
> RT
+ 2 K
set
> RT
+ 1 K
set
> RT
set
> RT
1 K
set
> RT
2 K
set
Possible change
C5:1
to
C5:127
C6:10
to
C6:127
d3:2
to
d3:35
d4: 13
to
d4:40
d5:1
Heating circuit pump "ON"
RT
< RT
+ 4 K
actual
set
RT
< RT
+ 3 K
actual
set
RT
< RT
+ 2 K
actual
set
RT
< RT
+ 1 K
actual
set
RT
< RT
actual
set
RT
< RT
1 K
actual
set
RT
< RT
2 K
actual
set
RT
< RT
3 K
actual
set
Minimum limit adjustable
from 1 to 127 °C (limited
by the boiler coding card)
Maximum limit adjustable
from 10 to 127 °C (limited
by the boiler coding card)
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 34)
Heating curve level ad-
justable from 13 to 40
(see page 34)
The external heating pro-
gram changeover
changes the heating pro-
gram to "Constant central
heating with standard
room temperature"
Coding
57

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ws3b

Table of Contents