Viessmann Vitodens 333 Service Instructions Manual page 75

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Fault codes
(cont.)
Display
Const.
Weath.
fault
comp.
code
bE
X
bF
X
C5
X
X
C6
X
C7
X
X
Cd
X
X
CE
X
X
System char-
Cause
acteristics
Control mode
Vitotrol re-
mote control
incorrectly
encoded
Control mode
Incorrect
LON com-
munication
module
Control mode,
Communica-
max. pump
tion error
speed
variable
speed inter-
nal pump
Control mode,
Communica-
max. pump
tion fault
speed
external vari-
able speed
heating cir-
cuit pump,
heating
circuit M2
Control mode,
Communica-
max. pump
tion fault
speed
external vari-
able speed
circulation
pump, heat-
ing circuit A1
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Control mode
Communica-
tion fault
ext. exten-
sion
Troubleshooting
Remedy
Check remote
control DIP switch
settings (see
page 105)
Replace the LON
communication
module
Check coding ad-
dress "30" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: OFF,
Switch 2: ON
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: OFF,
Switch 2: ON
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: ON,
Switch 2: OFF
Check connec-
tions, Vitocom 100
and coding ad-
dress "95"
Check connec-
tions and coding
address "2E"
75