Viessmann Vitodens 333 Service Instructions Manual page 83

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Repairs
(cont.)
3. Replace the sensor in case of
severe deviation.
Danger
The outlet temperature sen-
sor is immersed in the DHW
(risk of scalding).
Drain the secondary side of
the boiler before replacing
the sensor.
Checking the flue gas temperature sensor
The flue gas temperature sensor locks out the boiler when the permissible flue
gas temperature is exceeded. Reset the interlock after the flue gas system has
cooled down by pressing the reset "E" button.
1. Pull the leads from flue gas tem-
perature sensor A.
2. Check the sensor resistance and
compare it with the curve.
Troubleshooting
83