Viessmann Vitodens 333 Service Instructions Manual page 76

Compact gas fired condensing boiler. 4.2 to 19 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Display
Const.
Weath.
fault
comp.
code
CF
X
dA
X
db
X
dd
X
dE
X
E4
X
X
76
System char-
Cause
acteristics
Control mode
Communica-
tion fault
LON com-
munication
module
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
shorted out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
M2 shorted
out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
lead broken
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
M2 lead bro-
ken
Burner
Fault
blocked
ply voltage
24 V
Remedy
Replace the LON
communication
module
Check the room
temperature sen-
sor
heating cir-
cuit A1
Check the room
temperature sen-
sor
heating cir-
cuit M2
Check the room
temperature sen-
sor, heating cir-
cuit A1 and the
remote control
DIP switch set-
tings (see
page 105)
Check the room
temperature sen-
sor, heating cir-
cuit M2 and the
remote control
DIP switch set-
tings (see
page 105)
sup-
Replace the con-
trol unit