7.3
Wiring diagram
Key (Fig. 19)
C
Capacitor
E
Ignition electrodes
F
Flame sensor
MV
Fan motor
P
Short circuit socket
RS
Remote reset
SB
Remote lock-out signal (230V
TB
Burner earth
TL
Heat request thermostat
TS
Safety thermostat
V
Oil valve
XP5
5- pole socket
X5
5 pin plug
Electrical wiring
~ 50Hz - 230 V
General
switch
T4A
White
CARRIED OUT
IN THE FACTORY
~
- 0.5A max)
TO BE DONE BY
THE INSTALLER
CONTROL BOX
Black
White
Blue
WARNING
CAUTION
WARNING
23
GB
20068692
Test the burner by checking the shut-down of the
burner by opening the thermostats and the lockout
by darkening the flame sensor.
If the hood is still present, remove it and pro-
ceed with the electrical wiring according to
the wiring diagrams.
Use flexible cables in compliance with the EN
60 335-1 standard.
Do not invert the neutral with the phase in the
electrical supply line.
Check that the electrical supply of the burner
corresponds to that shown on the identifica-
tion label and in this manual.
The section of the conductors must be at
2
least 1mm
. (Unless otherwise required by
local guidelines and laws).
Fig. 19
20148053