Programming Menu; Shutdown Test; Light Diagnosis - Riello RDB 3.2 BX 32/50 Installation, Use And Maintenance Instructions

Kerosene burner
Hide thumbs Also See for RDB 3.2 BX 32/50:
Table of Contents

Advertisement

Available languages

Available languages

7.7

Programming menu

The programming menu can only be accessed via the reset push-
button or the remote reset during OPERATION.
If in page menu the reset push-button is not pressed, after 10
seconds occur automatic exit and there is a green led blinking for
the value set.
BLOCK DIAGRAM FOR ENTERING THE MENU
BURNER STATE
SWITCHING OFF
TYPE OF
TEST
FUNCTION
5 SECS.
NUMBER
2 RED
OF BLINKS
OUTLET
AUTOMATIC
OUTLET
S9155
Button release
Function
time
5s  t < 10s

Shutdown test

15s  t < 20s

Light diagnosis

20s  t < 25s
Intermittent
operation
25s  t < 30s
Last lockout
memorised
7.7.1
Shutdown test
Sequence for shutdown test
 Programming allowed in OPERATION.
 Press the button for 5 sec.  t < 10 sec.
 The RED LED blinks twice (0.2 sec. ON; 0.2 sec. OFF)
 Release the button
 The burner will initialise a shutdown followed by a restart
After shutdown, the burner restarts automatically and the number
of recycling attempts is restored.
At the exit of shutdown test page menu there are no leds flashing.
Electrical wiring
OPERATION (WITH FLAME)
BRIGHTNESS
DIAGNOSIS
15 SEC.
2 GREEN
10 SEC. AFTER
RELEASE
No. of Led
No. of pressings of the
blinks per
reset push-button
menu page
2 blinks
/
RED
none
2 blinks
1 = enabled
GREEN
2 = disabled (default)
3 blinks
1 = 0 disabled
GREEN
2 = 1 hour
3 = 24 hours (default)
4 blinks
/
GREEN
none
29
If the number of pressures on the push-button exceeds the max-
imum allowable, the value in memory will remain the maximum
one.
If the push-button or remote reset is pressed for more than 60
seconds, a failure of the push-button will be visualised and the
control-box will restart.
INTERMITTENT
OPERATION
20 SECS.
3 GREEN
10 SEC. AFTER
RELEASE
No. of Led
blinks (green)
/
none
1 blink
2 blink
1 blink
2 blink
3 blink
Displaying the type
of lockout accord-
ing to the table sec-
tion 7.5.2
7.7.2
Light diagnosis
Sequence for enable/disable
 Programming allowed in OPERATION.
 Press the button for 15 sec.  t < 20 sec.
 GREEN led flashing 2 times
 Release the button
 GREEN led OFF
 Press push-button 1 time for enable or 2 times for disable
function (*)
 GREEN led ON and OFF at every press and release
 After 10 sec., the GREEN LED will blink for the number of
times programmed (0.5 sec. ON; 0.5 sec. OFF).
GB
LAST LOCKOUT
MEMORISED
25 SECS.
4 GREEN
10 SEC. AFTER
RELEASE
Tab. I
Quitting the menu
Automatic, at the
end of the blinking
10 sec. after the release of
the button
10 sec. after the release of
the button
10 sec. after the release of
the button
Tab. J
20148053