7.7.3
Intermittent operation
Sequence for enable/disable
Programming allowed in OPERATION.
Press the button for 20 sec. t < 25 sec.
GREEN led flashing 3 times
Release the button
GREEN led OFF
Press push-button 1 time for disable function (*)
Press the button twice to enable a shutdown every 1 hour
(*)
Press the button 3 times to enable a shutdown every 24
hours (*)
GREEN led ON and OFF at every press and release
After 10 sec., the GREEN LED will blink for the number of
times programmed (0.5 sec. ON; 0.5 sec. OFF)
The modification of the intermittent operation setting parameter
takes effect:
–
after the activation of a switch-off test;
–
after flame disappearance during operation;
–
after disconnecting and reconnecting the electrical supply.
7.7.4
Display of the last lockout that occurred
The control box allows the last lockout that occurred and has
been
stored
to
be
displayed,
"7.7 Programming menu" on page 29
Access to this page is possible only Operating.
Display sequence of the last lockout that occurred
Keep the button pressed for 25 sec. = t < 30 sec.
The GREEN led blinks 4 times.
Release the button.
Display of the type of lockout stored for 10 sec.
The display time for the type of lockout can be extended by press-
ing the reset push-button during the display of the lockout (the
display of the lockout continues for another 10s).
NOTE:
(*) Always wait 1 sec. with each pressing and release of the
button to ensure the command is logged correctly.
20148053
Electrical wiring
by
accessing
of
See
30
GB