Faults / Solutions - Riello RDB 3.2 BX 32/50 Installation, Use And Maintenance Instructions

Kerosene burner
Hide thumbs Also See for RDB 3.2 BX 32/50:
Table of Contents

Advertisement

Available languages

Available languages

9

Faults / Solutions

Here below you can find some causes and the possible solutions
for some problems that could cause a failure to start or incorrect
operation of the burner.
A fault usually makes the lockout led signal which is situated in-
side the reset push-button of the control box.
Faults
The burner does not
start when there is heat
demand.
The burner goes into
lockout mode before or
during the pre-purging.
Burner runs normally in
the pre-purge and igni-
tion cycle and locks out
after 5 seconds ca.
Burner starts with an ig-
nition delay.
The manufacturer cannot accept responsibility for
any damage to persons, animals or property due
to error in installation or in the burner adjustment,
or due to improper or unreasonable use or non
WARNING
observance of the technical instruction enclosed
with the burner, or due to the intervention of un-
qualified personnel.
Faults / Solutions
Possible cause
Lack of electrical supply.
The flame sensor sees false light.
The connections in the control box
are wrongly inserted.
The heater is faulty or the P short-cir-
cuit socket is not connected (if there
is not a heater).
The flame sensor sees extraneous
light.
The flame sensor is dirty.
The flame sensor is faulty.
Flame moves away or fails.
The ignition electrodes are wrongly
positioned.
Air output is too high.
Nozzle dirty or worn.
When the lockout lamp comes on, the burner will only attempt to
start up after the reset push-button has been pressed. If ignition
is then normal, the stop can be attributed to a temporary fault that
is not dangerous.
If however the lock out continues the cause must be determined
and the solution found.
Fault
Solutions
diagnostics
OFF
Check presence of voltage in the L - N the pin plug.
Check the conditions of the fuses.
Check that safety thermostat is not lock out.
Eliminate the extraneous light.
OFF
Check and connect all the plugs and sockets prop-
erly.
Replace them.
Eliminate the extraneous light.
RED
Clear it.
Steady ON
Replace it.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
Check the coil of solenoid valve.
OFF
Adjust them according to the instructions of this
manual.
Set the air output according to the instructions of
this manual.
Replace it.
35
GB
Tab. M
20148053