5.12.2 Standard Wiring Diagram - Riello 40 GS10D Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

5.12.2 Standard wiring diagram

20126552
Key (Fig. 18)
AD
Air damper servomotor
B4
1st stage operating signal
B5
2nd stage operating signal
C
Motor capacitor
CN1
Ionisation probe connector
E
Ignition electrode
F
Filter
h1
1st stage hour counter
h2
2nd stage hour counter
MV
Fan motor
PA
Air pressure switch
PG
Min. gas pressure switch
S3
Lamp block (230V - 0.5A max.)
SO
Ionisation probe
TA
Ignition transformer
TB
Burner earth
TL
Limit thermostat
20063795
Installation
RMG88.62C2
TM
Burner shelf
TR
2nd stage thermostat
TS
Safety thermostat
T6A
Fuse
V10
Safety valve
V11
1st stage valve
V11
2nd stage valve
XP4
4-pole socket
XP6
6- pole socket
XP7
7-pole socket
X4
4-pin plug
X6
6 pin plug
X7
7 pin plug
WARNING
20
GB
*
*
Connect the 2nd stage thermostat
between terminals T6 and T8, re-
moving the bridge.
In the event of phase-phase power supply, a
bridge should be installed on the terminal board of
the control box between clamp 6 and the earth
clamp.
Fig. 18