Generac Power Systems PowerPact G0065201 Installation Manuallines page 37

50 hz air-cooled generators 5.6 kva
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
Installation Summary
1. Verify the installation has been properly performed
as outlined by the manufacturer and that it meets
all applicable laws and codes.
2. Test and confirm proper operation of the system as
outlined in the appropriate Installation and Owner's
Manuals.
3. Educate the end user on the proper operation,
maintenance and service call procedures.
Shutting Generator Down While
Under Load
IMPORTANT NOTE: To turn the generator off during
utility outages to perform maintenance, or conserve fuel,
follow these steps:
To turn the generator OFF (while running in AUTO
and online):
1. Turn the main utility disconnect OFF.
2. Turn the main line circuit breaker (MLCB) on the
3.
generator to OFF (OPEN).
4. Turn the generator OFF.
To turn the generator back ON:
1. Put the generator back into AUTO and allow to
start and warm-up for a few minutes.
2. Set the MLCB on the generator to ON.
The system will now be operating in automatic mode.
The main utility disconnect can be turned ON (CLOSED).
To shut the unit off, this complete process must be
repeated.
Installation Guidelines for 50 Hz PowerPact™
Control Panel/Start-up/Testing
33

Advertisement

Table of Contents
loading

Table of Contents