9.11 Setting the boiler's chimney
sweep function
With the boiler set to chimney sweep mode,
some automatic boiler functions can be dis-
abled, which makes checking and monitor-
ing operations easier.
• Enter "programming mode" by holding
down buttons 18 and 19 for 5 seconds
at the same time (Figure 9.14). The code
P00 appears on the display, indicating en-
try into "parameter P00" (Figure 9.15).
- 66 -
MAINTENANCE
13
14
Figure 9.14
Figure 9.15
Chimney sweep function at minimum
output in domestic hot water mode
• Scroll through the various parameters us-
ing 13 or 14 until the LCD display shows
the code P06, indicating entry into "pa-
rameter P06" (Figure 9.16).
Figure 9.16
• Press 17 (Figure 9.14) to show the value
of parameter P06 on the LCD display (Fig-
ure 9.17).
Figure 9.17
19
18
RESET
bar
RESET
bar
RESET
bar
17
16