Settings Record

This 7UT51 (version 3) settings worksheet enables
easy recording of 7UT51 parameter settings when
configuring the relay. The settings are listed in
numerical sequence based on Address just as they
appear on the LCD. Where applicable, value ranges
are provided for easy reference. Only configurable
settings are listed.
Addr LCD Line 1
WinDIGSI Description
TRANSFORMER DATA
1100
To configure 11xx settings, setting 7801 must first be set to one of the transformer types.
Vn WIND 1
1102
Rated voltage of transformer Winding 1
VA WIND 1
1103
Rated apparent power (VA) of Winding 1
In CT WND1
1104
Rated primary current of Winding 1 CT
CT1 STARPT
1105
-
Star
point formation of Winding 1 CT
Io1PROCESS
1106
Processing of Winding 1 zero sequence
current
In CT STP1
1107
Rated prim. current of Winding 1 star
CT
-
CT1 GND
PT
1108
Ground point formation of wind. 1
-
star
point CT
VECTOR GR2
1121
Vector group associated with winding 2
Vn WIND 2
1122
Rated voltage of transformer winding 2
VA WIND 2
1123
Rated apparent power (VA) of winding 2
In CT WND2
1124
Rated primary current of winding 2 CT
CT2 STARPT
1125
-
Star
point formation of winding 2 CT
Io2PROCESS
1126
Processing of winding 2 zero sequence
current
In CT STP2
1127
Rated prim. current of winding 2 star
CT
PRIM-2330C
Before configuring the device, copy this form and
enter the device identification number as well as the
date of configuration. Then simply mark an X beside
the desired options and enter numerical values in the
blank spaces provided. The factory defaults appear in
a column. Where different ranges and defaults apply
for the 1 amp and 5 amp nominal relays, the 1 amp
values are in parentheses below the 5 amp values.
After entering all data on this configuration form, take it
to the device and enter the information into the relay.
This form allows for the recording of all four setting
groups. Be sure to file a copy of this worksheet for
future reference.
Options or
Range and Unit
-
0.4
800.0 kV
-
0.2
5000.0 MVA
-
1
100000 A
Towards
Transformer
Towards line/busbar
-
Io
elimination
-
Io
correction
WITHOUT
-
1
100000 A
-
point
Towards transformer
Towards ground
-
0
11
-
0.4
800.0 kV
-
0.2
5000.0 MVA
-
1
100000 A
Towards transformer
Towards line/busbar
-
Io
elimination
-
Io
correction
WITHOUT
-
1
100000 A
-
point
Settings Record
Setting
Setting
Default
Group A
Group B
110.0
38.1
200
X
X
200
X
0
11.0
38.1
2000
X
X
2000
20
Setting
Setting
Group C
Group D
213