Field Testing and Commissioning
The polarities of the through flowing currents are
defined to be equal. When currents of equal phase
flow through the protected object, the angle difference
o
is 0
, provided the connections are correct. The
theoretical angle value depends on the protected
object, the transformers, and the connection group
entered into the relay (see Table 4.1 and Table 4.2).
The measured angles must be equal for all three
phases. If not, individual phases are interchanged.
The polarity of the current connections and the
parameterized polarity are taken into consideration
when the angles are displayed. Thus, if all three
o
angles differ by 180
from the theoretical value, the
polarity of one complete current transformer set is
wrong. This can be corrected by checking and
changing the corresponding plant parameters:
Address 1105 for the primary winding of a
transformer
Address 1125 for the secondary winding of a
transformer
Address 1206 for generators or motors
Address 1303 for Side 1 of a branch point
Address 1305 for Side 2 of a branch point
Note: The connection group of power transformers is
defined from the higher voltage side to the
lower voltage side. The angle (vector group *
30°) is valid only when measurement is carried
out in this way. That is, the test source is on the
higher voltage side and the short-circuit
200
bridges are on the lower voltage side. If
measurement is carried out from the lower
voltage side, the angle must be: 360° - vector
group*30°.
Address
Test Message
Test Angle L
-
I1L1
I2L1=0
4121
between the currents of Side 1, phase L1
against Side 2, phase L1, refer to
Table 4.1 and Table 4.2
Test Angle L
-
I1L2
I2L2=0
4121
between the currents of Side 1, phase L2
against Side 2, phase L2, should be 120
refer to Table 4.1 and Table 4.2
Test Angle L
-
I1L3
I2L3=0
4121
between the currents of Side 1, phase L3
against Side 2, phase L3, should be 120
refer to Table 4.1 and Table 4.2
Figure 18.4
WinDIGSI Screen example of the angle
measurement of the line currents.
Before the tests with symmetrical currents are
terminated, the differential and stabilizing currents are
checked. Even though the previous tests should have
detected all connection errors, nevertheless, errors
are possible concerning current matching and the
assignment of the connection group. Page to
Address 4161. In this Address, the calculated values
can be read out by scrolling through the display with
the No key or Backspace key. Note that the
differential and stabilizing values are referred to the
rated current of the protected object.
7UT51 v3
o
-
display of phase angle
o
-
display of phase angle
o
-
display of phase angle
PRIM-2330C
o
o