Numerical Listing Of User Definable Trip And Signal Functions - Siemens 7UT51 Instruction Manual

Protective relay
Hide thumbs Also See for 7UT51:
Table of Contents

Advertisement

13
Binary-Signal Inputs, Signal Contacts, Trip Contacts, and LED Indicators
13.7
Numerical Listing of User Definable Trip and Signal
Functions
The events listed below are the marshalling
possibilities for signal contact inputs, signal contact
outputs, trip contact outputs, and LEDs. Some events
are for transformer protection only and some are for
the 7UT513 only.
Event
LCD Abbreviation
1
not allocated
3
>Time Synch
4
>Trig. wave
5
>Reset LEDs
7
>ParamSelec.1
8
>ParamSelec.2
11
>UsrDefEvent1
12
>UsrDefEvent2
13
>UsrDefEvent3
14
>UsrDefEvent4
51
Relay OK
95
SetChg inProg
96
Set Group A
97
Set Group B
98
Set Group C
99
Set Group D
141
24V Failure
143
15V Failure
144
5V Failure
145
Offset Fail
151
I/O 1 Failure
152
I/O 2 Failure
161
I Supervision
163
Failure I symm
356
>Manual Close
391
>Buchh. Warn
392
>Buchh. Trip
393
>Buchh. Tank
501
Relay Pick
511
Trip
561
M/C Detect
571
Fail. I sym 1
572
Fail. I sym 2
573
Fail. I sym 3
132
Description
-
Clock
synchronizing binary
Trigger waveform capture
Reset LEDs
Change the active parameter set (must be used with a pair of binary
inputs, see Table 14.1 on page 144) when input becomes active.
>User defined event 1
>User defined event 2
>User defined event 3
>User defined event 4
Relay is operational and protecting (cannot be changed)
Setting change in progress
Setting group A is active
Setting group B is active
Setting group C is active
Setting group D is active
Failure of internal 24VDC power supply
Failure of internal 15VDC power supply
Failure of internal 5VDC power supply
Offset failure (A/D converter)
Failure in I/O module 1
Failure in I/O module 2
Failure: Current supervision
Failure: Current symmetry supervision
Manual Close command
Warning stage from Buchholz protection
Tripping stage from Buchholz protection
Tank Supervision from Buchholz protection
-
-
up
Relay Pick
up
General trip of the relay
Manual close command
Fail: Current symm. supervision Side 1
Fail: Current symm. supervision Side 2
Fail: Current symm. supervision Side 3
Note: Annunciations with a leading ">" sign are
identical with those for binary inputs and signal
or trip outputs. They represent the direct
confirmation of the binary input and are
available as long as the corresponding binary
input is energized.
-
signal input actuated.
7UT51 v3