Led Targets - Siemens 7UT51 Instruction Manual

Protective relay
Hide thumbs Also See for 7UT51:
Table of Contents

Advertisement

13
Binary-Signal Inputs, Signal Contacts, Trip Contacts, and LED Indicators
Relay
Relay 4
Relay 5
Relay 6
Relay 7
Relay 8
Relay 9
Relay 10
Relay 11
13.4

LED Targets

The LED targets on the front panel of the relay can be
controlled by the functions in section Table 13.1. One
LED indicates that the relay has power, while another
indicates when the relay is blocked. The other LEDs
can be configured. An LED lights when one of its
functions becomes active, and can be configured to
remain lit until reset (memorized, m) or only until the
function becomes inactive (not memorized, nm). The
7UT512 relay has six programmable LEDs, while the
7UT513 relay has 14.
6301 LED1
6302 LED 2
6303 LED 3
6304 LED 4
6305 LED 5
6306 LED 6
6307 LED 7 (7UT513 only)
Each LED can be independently lit by up to twenty functions (chosen from the list in Table 13.1). Each
function can cause the LED to remain lit until deliberately reset (memorized, m) or go out once the function is
no longer active (not memorized, nm) unless, of course, another function lighting the LED is still active. The
default configuration is listed below:
LED
Code
LED 1
511 Device Trip m
LED 2
5691 87
LED 3
5692 87HS Trip
LED 4
2451 BU Gen. Trip
128
Code
Function(s)
141
Failure 24V
143
Failure 15V
144
Failure 5V
145
Failure 0V
151
Failure I/O 1
152
Failure I/O 1
51 Device Operative
1571
O/L 1 Trip
1621
O/L 2 Trip
1566
O/L 1 warn
1616
O/L 2 warn
5821 RGF Gen. Trip
5921 Tank Gen. Trip
391 Buchh. Warn
392 Buchh. Trip
Function(s)
Description
General trip signal
-
Trip
87 Trip of differential protection
87HS Trip of differential protection
General Trip of backup overcurrent protection
Description
Relay failure
Thermal overload protection
Thermal overload protection
Trip of restricted ground-fault protection
Trip of tank leakage protection
Buchholz warning
Buchholz trip
Alarm functions have effect only when the
corresponding protection function is enabled and
active. Functions with a ">" sign prefix can be
assigned to both signal contact inputs and signal
contact outputs to pass a signal through the relay
independent of the relay's protective functions (of
course, the relay must be operational).
6308
LED 8 (7UT513 only)
6309
LED 9 (7UT513 only)
6310
LED 10 (7UT513 only)
6311
LED 11 (7UT513 only)
6312
LED 12 (7UT513 only)
6313
LED 13 (7UT513 only)
6314
LED 14 (7UT513 only)
7UT51 v3
PRIM-2330C