Capturing Waveform Data - Siemens 7UT51 Instruction Manual

Protective relay
Hide thumbs Also See for 7UT51:
Table of Contents

Advertisement

7UT51 v3
14.7

Capturing Waveform Data

5700 Operational Metered Values
5900 Thermal Overload Protection Calculated Values
Metered values are stored in these address. They are updated every 1 – 5 seconds.
LCD Abbreviation
Address
W1 Ia[%]=
W1 Ib[%]=
W1 Ic[%]=
W2 Ia[%]=
W2 Ib[%]=
W2 Ic[%]=
W3 Ia[%]=
W3 Ib[%]=
W3 Ic[%]=
IA[%]=
IB[%]=
W1 Ia=
W1 Ib=
W1 Ic=
W2 Ia=
W2 Ib=
W2 Ic=
W3 Ia=
W3 Ib=
W3 Ic=
IA=
IB=
Θ1/Θtrp
Θ1/ΘtrpA
Θ1/ΘtrpB
Θ1/ΘtrpC
Θ2/Θtrp
Θ2/ΘtrpA
Θ2/ΘtrpB
Θ2/ΘtrpC
The relay can record waveform data for the time just
before, during, and just after a fault. While this data
cannot be viewed on the front panel LCD, it can be
exported to a PC for analysis and viewing. The
sampling rate is 12 samples per power cycle. Data for
up to 3 faults is stored.
The storage of waveform data can be initiated in four
ways: (1) by the pickup of any active protection
function, (2) by the trip of any active protection
function, (3) by an external signal-contact input, or (4)
by a manual command using the front panel keypad.
PRIM-2330C
Description
5701
Current in winding (or side) 1 for phases A, B, and C as a percentage of the rated current.
5702
5703
5704
Current in winding (or side) 2 for phases A, B, and C as a percentage of the rated current.
5705
5706
5707
Current in winding (or side) 3 for phases A, B, and C as a percentage of the rated current
(7UT513 only).
5708
5709
5710
Additional current inputs when used and assigned (7UT513 only).
5711
5721
Current in winding (or side) 1 for phases A, B, and C in amps.
5722
5723
5724
Current in winding (or side) 2 for phases A, B, and C in amps.
5725
5726
5727
Current in winding (or side) 3 for phases A, B, and C in amps (7UT513 only).
5728
5729
5730
Additional current inputs when used and assigned in amps or milliamps, depending on
how configured (7UT513 only).
5731
5911
Temperature rise of 49
A, B, and C.
5912
5913
5914
5921
Temperature rise of 49
A, B, and C.
5922
5923
5924
Operation Using the Front Panel Controls
-
1 protection function for all phases, and separately for phases
-
2 protection function for all phases, and separately for phases
The waveform recording-time period is divided into
three parts: the pre-time, the middle-time, and the
post-time. The middle-time period begins when an
event initiates a fault log (a pickup, trip, contact-input,
or keypad-input). The middle-time ends with the
dropout of the protection function (for internally
initiated recordings), after a specified time period (for
recordings initiated by a signal-contact or a
keypad-input), or the external signal-input ends (an
option for recordings initiated by a signal-contact
input).