20
Settings Record
Addr LCD Line 1
WinDIGSI Description
M/C MODE P
Phase overcurrent stage effective: Manual
2121
close
-
49
THERMAL OVERLOAD PROTECTION LEVEL 1
2400
Password level = 2
49 Therml1
-
49
State of thermal O/L protection 1
2401
-
49 K
Fctr1
2402
-
-
9
K
factor for thermal O/L protection 1
49 Tconst1
2403
-
49
Time constant for thermal O/L prot 1
49 θ ALRM1
2404
-
49
Thermal alarm stage 1
I ALRM 1
2405
Current alarm stage 1
TEMP METH1
2406
-
49
Calculation method for thermal stage 1
-
49
THERMAL OVERLOAD PROTECTION LEVEL 2
2500
Password level = 2
49 Therml2
-
49
State of thermal O/L protection 2
2501
-
49 K
Fctr2
2502
-
-
9
K
factor for thermal O/L protection 2
49 Tconst2
2503
-
49
Time constant for thermal O/L prot 2
49 θ ALRM2
2504
-
49
Thermal alarm stage 2
I ALRM 2
2505
Current alarm stage 2
TEMP METH2
2506
-
49
Calculation method for thermal stage 2
TRANSFORMER TANK PROTECTION
2700
Password level = 2
TANK PROT
2701
State of transformer tank protection
TANK PU
-
2703
Pick
up value of transformer tank current
(for Insensitive CT A)
TANK PU
-
2704
Pick
up value of transformer tank current
(for Sensitive CT B)
MEAS.REPET
2705
Measurement repetition
TANK PU/DO
2709
-
Drop
out to pickup ratio for tank current
218
Options or
Default
Range and Unit
Inactive
X
50HS IOC w/o
Delay
50 Inverse w/o
Delay
OFF
X
ON
Block Tripping
Alarm Only
-
0.10
4.00
1.10
-
1.0
999.9 min
100.0
-
50
100 %
90
-
0.10
4.00 I/In
1.00
Theta MAX
X
Average \T
\T @ Imax
OFF
X
ON
Block Tripping
Alarm Only
-
0.10
4.00
1.10
-
1.0
999.9 min
100.0
-
50
100 %
90
-
0.10
4.00 I/In
1.00
Theta MAX
X
Average \T
\T @ Imax
OFF
X
ON
Block Tripping
-
0.10
10.00 I/In
0.50
-
10
1000 mA
500
Without Harmonics
X
With Harmonics
-
0.25
0.95
0.50
Setting
Setting
Setting
Group A
Group B
Group C
7UT51 v3
Setting
Group D
PRIM-2330C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents