12
Protection Self-Monitoring
12.5

Events and Actions

This table describes the events that control and are
generated by the self-monitoring features of the relay.
They are listed in numerical order by their event
identification number (shown in the "Event" column).
The text in the "LCD Abbreviation" column is the
corresponding text that will appear when viewing logs
on the front panel LCD display. In the "Oper" column, a
-
Protection Self
Monitoring Occurrence
-
Internal Self
Monitoring (see Section 12.2 on page 119)
Relay is operational and at least one protection function is active.
(This event is always marshalled to signal contact 5, and can be
marshalled to other contacts as well.)
LEDs have been reset
Parameters are being set
Wrong version of internal software
Wrong internal device identification
Annunciations lost (Operational Log buffer overflow)
Annunciations for PC lost
Fault annunciations lost (buffer overflow of a Fault Log)
Operational annunciations invalid
Fault annunciations invalid
LED annunciations buffer invalid
VDEW state invalid
Checksum error in memory
Checksum error in parameter set A
Checksum error in parameter set B
Checksum error in parameter set C
Checksum error in parameter set D
Failure of 24VDC internal power supply circuit
Failure of 15VDC internal power supply circuit
Failure of 5VDC internal power supply circuit
Analog/digital converters (offset failure)
Failure of I/O Module 1 (ZEA)
Failure of I/O Module 2 (ZEA, 7UT513 only)
Failure of RKA Module
LSA (data communication interface) disrupted
Monitoring of Supply Power (Section 12.3 on page 120)
Failure of the supply power de
relay.
Monitoring of CT Circuits (Section 12.4 on page 120)
Failure of current summation monitoring (only available when the
protected object is a bus)
Failure of current symmetry for at least one winding (or branch)
Failure of current symmetry for Winding 1 (or branch 1)
Failure of current symmetry for winding 2 (or branch 2)
Failure of current symmetry for winding 3 (or branch 3) (7UT513
only)
Table 12.1 Events Related to Protection Self
122
-
-
energizes the Self
Monitor signal
-
Monitoring
letter "C" or "G" indicates that the "Coming" and/or
"Going" events are logged in the Operational Log,
while if in the "Fault" column they indicate that the
events are logged in the open fault log. A letter in the
"In/Out" column indicates that the event can control an
LED and/or signal contact ("S"), and/or control a trip
(command) contact ("T").
LCD Abbreviation
Relay OK
LED Reset
SetChg inProg
-
Wrong SW
vers
Wrong dev. ID
Annunc. lost
Annu. PC lost
Flt.Buff.Over
Oper.Ann.Inva
Flt.Ann.Inval
LED Buff.Inva
-
VDEW
StateInv
Chksum Error
ChksumA Error
ChksumB Error
ChksumC Error
ChksumD Error
24 V Failure
15 V Failure
5 V Failure
Offset Fail
I/O 1 Failure
I/O 2 Failure
RKA Failure
LSA disrupted
I Supervision
Failure Isymm
Fail. Isym 1
Fail. Isym 2
Fail. Isym 3
7UT51 v3
Event
Oper
Fault
In/Out
0051
C G
0005
C
0095
C G
0100
C
0101
C
0110
C
0111
C
0115
C
0120
C
G
0121
C
G
0124
C
G
0129
C
G
0135
C
G
0136
C
G
0137
C
G
0138
C
G
0139
C
G
0141
C
G
0143
C
G
0144
C
G
0145
C G
0151
C
G
0152
C
G
0154
C
G
0159
C
G
0161
0163
C
G
0571
C
G
0572
C
G
0573
C
G
PRIM-2330C
S
S
S
S
S
S
S
S
S
S
S
S
S