2.7
Phase Differential Protection of a Transformer
(87T and 87HS)
Settings
Operational status
Minimum differential current required for pickup (87T)
Maximum differential current allowed before pickup (87HS)
Restraint based on total current level
-
Restraint for through
fault causing CT saturation
Inrush restraint based on 2nd harmonic current
Restraint based on 3rd, 4th, or 5th harmonic current
Time delay before trip (separate settings for 87T and 87HS) 0.00 to 60.00 s (step 0.01 s), or ∞
Time delay before reset
Events that can control signal contacts or trip contacts
Inherent Operating Times
-
Pickup time with single
ended infeed:
≥ 1.5 times 87T pickup threshold level (approx.)
I
DIFF
≥ 1.5 times 87HS pickup threshold level (approx.)
I
DIFF
≥ 5.0 times 87HS pickup threshold level (approx.)
I
DIFF
Dropout time (approximate)
Dropout Ratios
87T and 87HS dropout ratios
(dropout/pickup; approximate)
Operating Tolerances (with default settings)
Pickup characteristic
Inrush restraint
Set time delays
Effect of Environmental Influences on Times and Tolerances
Supply power voltage
Ambient temperature
System frequency
Table 2.4
Specifications for Phase Differential Protection of a Transformer (87T and 87HS) (details in Chapter 4)
PRIM-2330C
-
Active, inactive, or block
contacts; can be temporarily
-
changed using binary
signal inputs
0.15 to 2.00 times I
(0.01 steps)
n
0.5 to 20.0 times I
(0.01 steps)
n
Characteristic with two sloped segments (see Figure 4.9)
Through current 5.00 to 15.00 times I
of restraint (2 to 250 cycles, or ∞); relay can detect an
evolving internal fault and release this restraint.
10% to 80% of fundamental current (step 1%); option to
crossblock other phases for a selectable duration (in
cycles); is released when the differential current exceeds
87HS.
10% to 80% of fundamental current (step 1%); option to
crossblock other phases for a selectable duration (in
cycles); is released when the differential current exceeds a
set value (0.5 to 20.0 times I
0.00 to 60.00 s (step 0.01 s)
Change in operational status; pickup events, start of time
delay before trip; start and end of restraint; trip events. All
events are logged, as are the differential and restraint
current levels at the time of a trip.
60 Hz
35 ms
35 ms
25 ms
17 ms
18 ms
25 ms
30 ms
0.7
±5% of characteristic value (for I < 5× I
±5% of setting value (for I
2nd harmonic
±1% of setting value or 10 ms, whichever is greater
≤ 1% if between 80% and 115% of nominal voltage
≤ 0.5% / 10 K if between 0°C and 40°C (32°F and 104°F)
≤ 1% if between 95% and 105% of nominal frequency.
Note: 87T function is blocked when frequency is less
than about 85% of the nominal frequency, or more
than about 120%; see Figure 4.12.
Description of Relay
(step 0.01); duration
n
, step 0.1)or 87HS.
n
-
50 Hz
16
2/3 Hz
85 ms
25ms
55 ms
25 ms
90 ms
)
n
≥ 15% of I
fundamental
2
)
21