20
Settings Record
Addr LCD Line 1
WinDIGSI Description
87HS DELAY
1626
-
87
Op time of high
87 RESET
1627
-
87
Reset dly after diff op has been initiated
-
87
MOTOR/GENERATOR DIFF PROTECTION DATA
1700
Password level = 2
87 STATUS
1701
-
87
State of differential protection
87 PICKUP
1703
-
-
87
Pick
up value of diff protection
87SLOPE 1
1706
-
87
Slope 1 of operating characteristic
87BASE PT2
1707
-
87
Base point for slope 2 of oper charact.
87SLOPE 2
1708
-
87
Slope 2 of operating characteristic
-
-
T
SAT
BLK
1717
-
87
Max. blocking time at CT saturation
-
SAT
RESTR.
1718
-
87
Min. restr. current for block at CT satur.
87 DELAY
1725
-
87
Oper time delay of differential
protection
87 RESET
1727
-
87
Reset delay after trip has been initiated
-
87
TIE POINT DIFFERENTIAL PROTECTION DATA
1800
Password level = 2.
87 STATUS
1801
-
87
State of differential protection
87 PICKUP
1803
-
-
87
Pick
up value of diff protection
87SLOPE 1
1806
-
87
Slope 1 of operating characteristic
87BASE PT2
1807
-
87
Base point for slope 2 of operating char
87SLOPE 2
1808
-
87
Slope 2 of operating characteristic
-
-
T
SAT
BLK
1817
Max. blocking time at CT saturation
-
SAT
RESTR.
1818
-
87
Min. restr. current for blocking @CT
satur.
-
87
DELAY
1825
-
87
Oper time delay of differential
protection
-
87
RESET
1827
-
87
Reset delay after trip has been
initiated
87 MON PU
1831
-
-
87
Pick
up value of diff. current monitoring
87 MON DLY
1832
-
87
Time delay of blocking by monitoring
216
0.00
-
set diff. curr stage
0.00
OFF
ON
Block Tripping
0.05
0.10
0.0
0.25
2
5.00
0.00
0.00
OFF
ON
Block Tripping
0.30
0.10
0.0
0.25
2
5.00
Junct
0.00
0.00
0.15
1
Options or
Default
Range and Unit
60.00 s or ∞
-
0.00
-
60.00 s
0.10
X
-
2.00 I/In M/G
0.10
-
0.50
0.12
-
10.0 I/In M/G
2.5
-
0.95
0.50
250 cycles or ∞
-
8
-
15.00 I/In M/G
7.00
60.00 s or ∞
-
0.00
-
60.00 s
0.10
X
-
2.50 I/In Junct
1.00
-
0.50
0.25
-
10.0 I/In Junct
2.5
-
0.95
0.50
250 cycles or ∞
-
8
-
15.00 I/In
7.00
60.00 s or ∞
-
0.00
-
60.00 s
0.10
-
0.80 I/In Junct
0.20
10 s or ∞
-
2
Setting
Setting
Setting
Group A
Group B
Group C
7UT51 v3
Setting
Group D
PRIM-2330C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents