Binary-Signal Inputs, Signal Contacts, Trip Contacts, and LED Indicators
7UT51 v3
LCD
Event
Abbreviation
>BU50HS BLK
2306
>BU50/51 BLK
2307
>Ext1 BLOCK
4523
>Ext1 blkTRIP
4525
>Ext1 TRIP
4526
>Ext2 BLOCK
4543
>Ext2 blkTRIP
4545
>Ext2 TRIP
4546
>87Diff BLOCK
5603
>87DiffBlkTrip
5605
>RGF BLOCK
5803
>RGF blk Trip
5805
>Tank BLOCK
5903
>Tank blkTrip
5905
13.3

Signal Output Contacts

13.3.1

Programmable Signal Contacts

Signal contact outputs enable the relay to send signals
to other devices by closing (or opening) the
connection between a pair of terminals. Each signal
contact output is controlled by up to twenty functions
selected from Table 6.x. The 7UT512 relay has four
contact outputs and the 7UT513 relay has ten contact
outputs. If desired, a function can activate more than
one signal contact relay.
6201 SIGNAL CONTACT 1
6202 SIGNAL CONTACT 2
6203 SIGNAL CONTACT 3
6204 SIGNAL CONTACT 4
6205 SIGNAL CONTACT 5
Each signal relay can be independently activated by up to twenty (20) functions (chosen from the
list in section Table 13.1). The default configuration is listed below:
Relay
Relay 1
Relay 2
Relay 3
PRIM-2330C
Effect of Input Signal
Block 50HS stage of backup O/C
Block 50/51 stage of backup O/C
External Trip 1 signal (received through another signal input) will be blocked, will be
blocked from causing a trip ( ), or will be issued by a signal to this discrete input ( ).
BLOCK external trip 2
BLOCK trip signal of external trip 2
External trip 2
BLOCK differential protection
BLK differential prot. trip signal
-
Block restricted ground
fault protect
Block trip of restricted ground
Block transformer tank protect
Block transformer tank protect trip signal
Code
Function(s)
511 Device Trip
5671 Diff Gen Trip
2451 Back Gen Trip
-
fault
Alarm functions have effect only when the
corresponding protection function is enabled and
active. Functions with a ">" sign prefix can be
assigned to both signal contact inputs and signal
contact outputs to pass a signal through the relay
independent of the relay's protective functions (of
course, the relay must be operational).
7UT513 Only
6206 SIGNAL CONTACT 6
6207 SIGNAL CONTACT 7
6208 SIGNAL CONTACT 8
6209 SIGNAL CONTACT 9
6210 SIGNAL CONTACT 10
6211 SIGNAL CONTACT 11
Description
General trip signal
Trip of differential protection
Trip of backup overcurrent time protection
13