Setting Problems

5-2

Setting Problems

5-2-1

Unable to Set Scaling

Scaling cannot be set in the following cases.
• When scaling is performed outside the measurable range when a
Reflective Sensor Head is used.
• When the distance (or width) of two-point scaling is less than 10% of full
scale (FS).
• When the numeric value for scaling input is extremely small or large.
5-2-2

Unable to Set Monitor Focus

The monitor focus cannot be set when specified distances (or widths)
between two points is less than 10% of full scale (FS).
Set the monitor focus after performing scaling.
It is recommended that the linear output value for display value be deter-
mined using the scaling after setting the display value for actual distances
(or widths).
5-2-3

Unable to Set Threshold Values

Always set threshold values to satisfy the following formula:
HIGH threshold value > LOW threshold value
In addition, the threshold values cannot be set if the PASS judgement can-
not be made because the hysteresis (Hys) is too large and the following
equation is true:
(HIGH threshold value − LOW threshold value) < Hys
5-2-4

Unable to Set Hysteresis

The hysteresis cannot be set if the PASS judgement cannot be made
because the hysteresis (Hys) is too large and the following equation is
true:
(HIGH threshold value − LOW threshold value) < Hys
Decrease the setting of the hysteresis to eliminate the above condition.