Installation sequence
Installing the external unit
Wall mounting
Installation must be completed with the
bracket set for wall mounting (acces-
sory).
Separate installation instructions

Installing the internal unit

!
Please note
Avoid damaging the appliance
during transportation.
Never put weight on top of the
appliance.
Installation room requirements
!
Please note
The installation room must be dry
and free from the risk of frost.
Ensure ambient temperatures of
0 to 35 ºC.
!
Please note
Avoid dust, gases and vapours
due to a risk of explosion
in the installation room.
28
(cont.)
Note
Wind loads must be considered when
installing the unit on external walls or
roofs.
Minimum room volume (to
DIN EN 378):
Type AWB/AWB-
AC
201.A04
201.A07
201.A10
201.A13
Minimum room
3
volume in m
2.7
4.8
6.7
6.7