Omron SYSMAC NY Series Hardware User Manual page 190

Ipc machine controller industrial panel pc
Hide thumbs Also See for SYSMAC NY Series:
Table of Contents

Advertisement

7 Maintenance
4
Replace the complete Fan Unit.
1
1) Push the lever
2) Lift the lever to tilt
3) Remove
5
Insert the new Fan Unit in the Panel PC.
Ensure the end of the Fan Unit A is positioned under the fan guide B .
6
Connect the Fan Connectors to the board.
7
Mount the Cover.
8
Power ON the system.
Confirm both fans rotate immediately after Power ON.
The fans are replaced and the alarm is automatically reset.
7-8
3
2
1
to unlock the Fan Unit.
2
the Fan Unit.
3
the complete Fan Unit.
A
NY-series Industrial Panel PC Machine Controller Hardware User's Manual (W557)
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac ny532-1 00 seriesSysmac ny532-5400

Table of Contents