Omron SYSMAC NY Series Hardware User Manual page 174

Ipc machine controller industrial panel pc
Hide thumbs Also See for SYSMAC NY Series:
Table of Contents

Advertisement

5 Installation
Connect UPS Using the I/O Connector
The I/O connector of the IPC Machine Controller
• receives the power status of the UPS with the UPS Mode Input.
• indicates the power status of the Panel PC to the UPS with the Power Status Output when the Panel
PC has a Windows operating system. For other operating systems this output is not functional.
The Panel PC will shut down properly in case of a power supply interruption.
Precautions for Safe Use
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS to the I/O connector of the Panel PC and to config-
ure it correctly.
Refer to 5-4-4 Wire the I/O Connector on page 5-37 for I/O Connector details.
1
Ensure the revision number of the UPS is correct.
Refer to 3-10-10 UPS on page 3-33 for more information.
2
Connect and install the S8BA UPS.
Refer to the UPS S8BA User's Manual (Cat. No. U702) for details.
Connect the Contact port of the S8BA UPS to the I/O port of the Panel PC with the connection
cable S8BW-C02.
Power Supply (S8VK)
AC (L)
AC (N)
3
Power ON the Panel PC.
5-44
UPS (S8BA)
24 VDC
Input
24 VDC
0 VDC
NY-series Industrial Panel PC Machine Controller Hardware User's Manual (W557)
Output
24 VDC
0 VDC
COM
4
1
BU
6
BS
Contact
IPC Product
6
UPS Mode Input
5
UPS Mode Input
2
Power Status Output
1
Power Status Output
I/O

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac ny532-1 00 seriesSysmac ny532-5400

Table of Contents