Code 2; Calling Up Code 2 - Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors

Pellet boiler
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Start delay
D2:10
Start delay of the additional heat
source of 10 min
Start temperature set system temperature
D3:-10
Start temperature of the additional
heat source. Condition for starting:
Actual system temperature < set
system temperature minus value
set (here: 10 K)
Minimum runtime
D4:5
Minimum runtime of the additional
heat source of 5 min
Minimum pause duration
D5:5
Minimum pause duration of the ad-
ditional heat source of 5 min
Start without delay, Set system temp
D6:-20
Start of additional heat source
without delay. Condition: Actual
system temperature < set system
temperature minus value set (here:
20 K)
Parallel operation
D7:1
Parallel operation of both heat
sources is possible.
Note
Parallel operation only possible
when the additional heat source
has a boiler circuit pump.

Code 2

Calling up code 2

Note
At coding level 2, all codes are accessible, including
the codes at coding level 1.
Codes that are not assigned, due to the heating sys-
tem equipment level or the setting of other codes,
are not displayed.
Press the following keys:
1.
+
simultaneously for approx. 4 s.
d
å
The "Service" menu appears.
Possible change
D2:0
Adjustable value in min
to
D2:250
D3:-100
Adjustable value in K
to
D3:-1
D4:0
Adjustable value in min
to
D4:250
D5:0
Adjustable value in min
to
D5:250
D6:-100
Adjustable value in K
to
D6:0
D7:0
Parallel operation of both boilers is
not possible.
2.
simultaneously for approx. 4 s.
+
d
ä
"Code 2" appears in the "Service"
menu.
3.
/
for "Code 2".
|
~
4.
to confirm.
d
5.
/
for the required coding address.
|
~
6.
to confirm.
d
7.
/
for the required value.
|
~
Codes
61