Codes
Code 2
(cont.)
Parameter address
Frost protection function / heating cir-
"A3"
cuit pump "On"
6
7 °C
5
6 °C
4
5 °C
3
4 °C
2
3 °C
1
2 °C
0
1 °C
1
0 °C
2
1 °C
to
to
15
14 °C
Coding
Coding in the delivered condition
Frost protection activation
A4:0
The frost protection function is ac-
tivated. Start and stop tempera-
tures of the function can be adjus-
ted (code "A3", heating group).
Frost protection function: The heat-
ing circuit pump is switched on at
the relevant outside temperature; a
minimum flow temperature of
10 °C is specified. At the relevant
outside temperature, it is automati-
cally switched off.
Room sensor offset
E2:50
Is available if code "A0:1" or
"A0:2", heating group, is set.
No correction of actual room tem-
perature
Screed drying
F1:0
Screed drying disabled

Boiler

Coding
Coding in the delivered condition
Flue gas residual O2, partial load correction
0D:2.0
2.0 % correction of set value for
concentration of residual oxygen in
the flue gas, depending on the cur-
rent boiler output
64
Frost protection function / heating circuit
pump "Off"
5 °C
4 °C
3 °C
2 °C
1 °C
0 °C
1 °C
2 °C
3 °C
to
16 °C
Possible change
A4:1
The frost protection function is disa-
bled. Adjustment only possible if
code "A3:−9" has been set.
Note
Observe the note for code "A3".
E2:0
Correction - 5 K to display correction
to
- 0.1 K
E2:49
E2:51
Display correction + 0.1 K to display
to
correction + 4.9 K
E2:99
F1:1
Screed drying adjustable in accord-
to
ance with 6 selectable tempera-
F1:6
ture:time profiles (for more informa-
tion, see chapter "Screed drying").
Possible change
0D:0
Setting range 0.0 to 5.0
to
0D:5.0

Advertisement