Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors page 65

Pellet boiler
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
Boiler water temperature, delay
0F:60
Shutdown delay of 60 s when max.
boiler water temperature is excee-
ded (code 1, address E, Boiler
group)
Flow controller active
11:0
Regulation of the boiler flow tem-
perature is disabled
Minimum set system temperature
13:1
If the heating circuits are not regu-
lated by the boiler control unit, a
minimum set system temperature
can be selected.
Minimum boiler pump speed
1C:30
Min. speed of the boiler circuit
pump is 30 % of the max. speed.
Maximum boiler pump speed
1D:100
Boiler circuit pump speed is
100 %.
Minimum flue gas temperature
3F:70
Limitation of min. flue gas temper-
ature to 70 °C
Output controller
46:10
Response speed of the boiler out-
put controller
Material controller
47:7
Speed of the boiler material con-
troller
Material controller, delay
4A:100
100 s delay of fuel delivery on fuel
ignition
Material controller limit (full load)
53:...
If the air damper exceeds the se-
lected value in %, the amount of
fuel supplied is reduced.
Delivered condition for boiler out-
put:
8 kW: 60
12 kW: 75
18 to 48 kW: 80
Possible change
0F:0
Setting range in s
to
0F:240
11:1
Regulation of the boiler flow temper-
ature is enabled
13:0
Setting of min. set system tempera-
ture is disabled.
1C:10
Setting range in %
to
1C:100
1D:10
Setting range in %
to
1D:100
3F:50
Setting range in °C
to
3F:150
46:5
Setting range: a small value slows
to
the controller down; a large value
46:15
speeds it up.
47:5
Setting range: a small value slows
to
the controller down; a large value
47:15
speeds it up.
4A:1
Setting range in s
to
4A:240
53:...
Setting range in % for boiler output:
to
8 kW: 25 to 80
53:...
12 kW: 25 to 95
18 to 48 kW: 10 to 95
Codes
65