Heating - Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors

Pellet boiler
Table of Contents

Advertisement

Codes
Code 1
(cont.)

Heating

Coding
Coding in the delivered condition
Remote control
A0:0
Available if a remote control is be-
ing connected.
Without remote control
Summer eco function room temperature
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump "Off" when outside
temperature (OT) is 1 K higher
than the set room temperature
(RT
set
Parameter ad-
Heating circuit pump "Off"
dress "A5":
Summer eco function active
1
OT
2
OT
3
OT
4
OT
5
OT
6
OT
7
OT
to
to
15
OT
Coding in the delivered condition
Summer eco function, absolute
A6:36
Extended economy mode disabled A6:5
54
)
RT
+ 5 K
>
set
RT
+ 4 K
>
set
RT
+ 3 K
>
set
RT
+ 2 K
>
set
RT
+ 1 K
>
set
RT
>
set
RT
1 K
>
set
RT
9 K
>
set
Possible change
A0:1
With Vitotrol 200A. Recognised au-
tomatically.
A0:2
With Vitotrol 300A. Recognised au-
tomatically.
A0:3
With Vitotrol 350. Recognised auto-
matically.
A5:0
Without heating circuit pump logic
function
A5:1
With heating circuit pump logic func-
to
tion (see the following table)
A5:15
Possible change
Extended economy mode active, i.e.
to
the heating circuit pump is switched
A6:35
off at a variable value, adjustable
from 5 to 35 °C plus 1 °C. The mixer
is closed. This value is based on the
adjusted outside temperature, com-
prising the actual outside tempera-
ture and a time constant. The time
constant takes into account the cool-
ing down of an average building.
Recommended setting: "A6:16" to
"A6:18"