Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors page 51

Pellet boiler
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Feed screw conveyor, maximum cycle
15:...
Max. cycle limit of feed screw con-
veyor in %.
Delivered condition for boiler out-
put:
8 kW: 90
12 kW: 95
18 kW: 75
24 kW: 95
32 kW: 75
40 kW: 85
48 kW: 95
Day hopper idle runtime (man. charging)
27:100
Rotary lock valve idle runtime of
100 minutes if boiler charged man-
ually. Code only available if boiler
charged manually.
Day hopper idle runtime (autom. charging)
2C:...
Rotary lock valve idle runtime in
minutes before vacuum module
starts. Code only available if boiler
charged automatically.
Delivered condition for boiler out-
put:
8 and 12 kW: 200
18 to 48 kW: 250
Screw conveyor, delay
2E:2
Delay, 2 s
Discharge, cycle ON
30:5
Discharge cycle, 5 s
(discharge runs for 5 s)
Discharge, cycle OFF
31:0
Discharge cycle, 0 s
(discharge does not pause: contin-
uous operation)
Discharge, delay
32:5
Delay, 5 s
External charging, cycle ON
40:5
Cycle of external charging, 5 s
(external charging runs for 5 s)
External charging, cycle OFF
41:0
Cycle of external charging, 0 s
(external charging does not pause:
continuous operation)
Possible change
15:10
Setting range in %
to
15:100
27:1
Setting range in min
to
27:1000
2C:1
Setting range in min
to
2C:1000
2E:0
Setting range in s
to
2E:100
30:2
Setting range in s
to
30:250
31:1
Setting range in s
to
(discharge pause adjustable from 1
31:100
to 100 s)
32:0
Setting range in s
to
32:100
40:2
Setting range in s
to
40:250
41:1
Setting range in s
to
(pause in external charging adjusta-
41:100
ble from 1 to 100 s)
Codes
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vl3c

Table of Contents