Sensors; Connection; Checking Sensors - Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors

Pellet boiler
Table of Contents

Advertisement

High limit safety cut-out
3. Close cover
A
on the programming unit.

Sensors

Sensor type Pt1000:
Flow temperature sensor
Buffer temperature sensor
Return temperature sensor
Flue gas temperature sensor
Outside temperature sensor

Connection

See chapter "Connection and wiring diagram" from
page 117.

Checking sensors

Flue gas temperature sensor
1.75
1.25
0.75
A
50
0
Temperature in °C
Fig. 40
Data point shown: Resistance of 1.1 k
A
perature of 25 °C
Further sensors
1.20
1.15
1.10
1.05
1.00
0.95
0.90
0.85
-30
-20
-10
Temperature in °C
Fig. 41
1. Pull out corresponding plug.
(cont.)
150
100
at a tem-
Ω
0
10
20
30
40
4. Acknowledge excess temperature at the program-
ming unit of the control unit with
Curve of the sensor from the extension kit for heating
circuit with mixer:
Extension kit installation instructions
200
250
50
2. Check the sensor resistance at the plug.
Maintenance