Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 138

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Function description
Control functions
(cont.)
Heating curve (level and slope)
90
80
70
60
50
40
30
10
Fig. 84
Example for outside temperature of -14 °C:
Underfloor heating system, slope 0.2 to 0.8
A
Low temperature heating system, slope 0.8 to 1.6
B
Heating system with a boiler water temperature in
C
excess of 75 °C, slope 1.6 to 2.0
Upper control range limit
Electronic maximum temperature limit
Setting range: 10 to 100 °C
Change via coding address "C6"
Note
The maximum temperature limit is no substitute for
the underfloor heating system temperature limiter.
Temperature limiter for underfloor heating:
If the selected value is exceeded, the temperature
limiter stops the heating circuit pump. The flow tem-
perature decreases only slowly, i.e. it may be several
hours before the system restarts automatically.
Cylinder temperature control
Cylinder temperature control is a constant temperature
control. It operates by starting and stopping the circula-
tion pump for cylinder heating.
The switching differential is 10 K.
Central heating is switched off during cylinder heating
(when cylinder priority control is activated. See
code "A2", heating group).
Coding addresses
Coding addresses that influence cylinder tempera-
ture control:
0C, 0D (DHW group)
A2 (Heating group)
For a description, see the relevant coding address in
chapter "Codes".
138
Slope
0
-10
-20
-14
Outside temperature in °C
1.4
C
1.2
1.0
B
0.8
0.6
0.4
A
0.2
-30
Lower control range limit
Electronic minimum temperature limit
Setting range: 10 to 100 °C
Change via coding address "C5"
Only active during operation with standard room tem-
perature.