Coding in the delivered condition
Transfer heat
44:100
Heat is transferred from the coded
heating circuits, starting at a boiler
water temperature of 100 °C.
Material controller
46:...
Speed of boiler material controller
Output controller
47:...
Speed of boiler output controller
Boiler water temperature delay
49:60
Shutdown delay of 60 seconds if
the max. flow temperature of the
boiler is exceeded
Material controller, delay
4A:...
Delay of fuel delivery in seconds
on fuel ignition
Light barrier, firebed cycle ramp
52:...
Cycle ramp setting for the feed
screw conveyor when firebed light
barrier is interrupted in seconds
Material controller, flue gas fan
55:...
Factor for varying fan speed
Material controller, minimum limit
56:...
Min. air damper position in % at
partial load
O2 control active
5F:0
Control via flue gas oxygen con-
tent not active
5F:2
Cannot be adjusted
Status message in the case of a
fault.
Flow controller active
60:1
Control of flow active
60:2
Flow control via boiler circuit pump
Only possible for boiler circuit
pumps with PWM signal.
Possible change
44:70
Setting range in °C
to
44:120
46:1
A small value slows the controller
to
down, a large value speeds it up.
46:30
47:1
A small value slows the controller
to
down, a large value speeds it up.
47:30
49:0
Setting range in seconds
to
49:240
4A:1
Setting range in seconds
to
4A:420
52:1
Setting range in seconds
to
52:50
55:0
Setting range without unit
to
55:50
56:1
Setting range in %
to
56:190
5F:1
Control via flue gas oxygen content
active
60:0
Control of flow not active
Codes