Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 113

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Checking operating states, actuators and sensors
Operating states, actuators and sensors can be
checked in the following menus:
Under "Information"
Submenu in the extended "Standard menu".
Under "Diagnosis"
Submenu in the "Service" menu.
Note
Check the temperature values or states of the indica-
ted inputs for "function and logic".
Calling up the "Information" menu
Press the following keys:
1.
"Menu" appears.
å
2.
/
for "Information".
|
~
Calling up the "Diagnosis" menu
Press the following keys:
1.
+
simultaneously for approx. 4 s.
d
å
The "Service" menu appears.
2.
/
for "Diagnosis"
|
~
Checking the outputs (actuators)
Danger
Incorrectly connected actuators can cause dam-
age to the system.
During the actuator tests, check the respective
actuator carefully.
Danger
Activated charging devices (feed screw con-
veyor, screw conveyor, etc.) can cause block-
ages in the fuel discharge system during the
actuator test.
Activate charging devices only briefly.
The following actuators can be switched "manually"
Depending on boiler size and settings, other actuators
may be available.
"General"
"Central fault Open"
"Output On"
Diagnosis and service checks
Examples of "function and logic":
Are the temperature values of the sensors in the nor-
mal range?
Is the state of the maintenance cover (open or
closed) correct?
Is the state of the light barrier (free or interrupted)
correct?
Residual oxygen content OK?
3.
to confirm.
d
4.
/
+
for the required information in the
d
|
~
menu.
5.
until the default display is shown.
ä
3.
to confirm.
d
4.
/
+
for the required information in the
d
|
~
menu.
5.
until the default display is shown.
ä
The following displays appear in sequence:
"General"
"Boiler"
"Charging"
"Flue gas filter"
"Additional boiler"
"Heating circuit 1"
"Heating circuit 2"
"Heating circuit 3"
"Heating circuit 4"
"DHW"
"DHW circulation"
"Solar"
"Boiler"
"Flue gas fan On"
"Ignition On"
"Prim air damper Open"
"Prim air damper Close"
"Sec air damper Open"
"Sec air damper Close"
"Boiler pump On"
113

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vh3

Table of Contents