Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 108

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
Cleaning blocking
63:0
Do not block heat exchanger
cleaning of the boiler.
Primary air damper, maximum limit
82:...
Max. position of primary air damp-
er in % at full load
Primary air damper, minimum limit
83:...
Min. position of primary air damper
in % at partial load
Lambda probe, automatic system
F9:1
Automatic start of Lambda probe
heating
Calibration of Lambda probe
manual only
O2 probe type
FF:0
Lambda probe used: Type LSM 11 FF:1
Charging
Different codes will be available depending on the set
"Charging scheme".
Coding
Coding in the delivered condition
Run feed until empty
05:1
Feed is run until empty.
Terminate 'run feed until empty' at
17:16
Emptying of the feed is terminated
when the residual oxygen content
of the flue gas is 16 %.
Feed screw conveyor temperature
18:70
Max. temperature of the feed
screw conveyor, 70 °C
108
Possible change
63:1
Blocking times for heat exchanger
cleaning from 22:00 to 06:00.
63:2
Blocking times for heat exchanger
cleaning from 21:00 to 07:00.
63:3
Blocking times for heat exchanger
cleaning from 20:00 to 08:00.
63:4
Blocking times for heat exchanger
cleaning from 19:00 to 09:00.
82:5
Setting range in %
to
82:100
83:5
Setting range in %
to
83:100
F9:0
Lambda probe heating always on
Calibration of Lambda probe man-
ual only
F9:2
Automatic start of Lambda probe
heating
Automatic calibration of Lambda
probe
Lambda probe used: Type NGK
FF:2
0 to 20 mA
FF:3
Lambda probe used: Wideband
probe with BLS
Possible change
05:0
Feed is not run until empty.
17:10
Setting range in %
to
17:20
18:20
Setting range in °C
to
18:250