Page 40 of 220 Installing the hardware
Installing a lightning surge arrestor
553-3601-200 Standard 7.00 November 1998
Install the lightning surge arrestor to protect the Meridian 1 system from
electrical surges.
1.
Mount the lightning surge arrestor on the interior wall as close as
possible to the entry point of the coaxial cable from the outdoor external
antenna (see Figure 19).
Figure 19 : Lightning surge arrestor and bracket
2.
Before you connect the ground lead to the lightning surge arrestor, attach
it to an approved ground.
The recommended wire gauge is 6 AWG. Connect the ground lead to the
building ground. Do not connect to a ground rod or series of ground
rods. If you cannot connect the ground lead to the building ground,
connect it to the steel frame of the building. (The connection should be
no more than 6 to 10 ft.)