SECTION 8 - MICROPANEL
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.
Table 23 - Setpoint limits
Program value
Leaving chilled liquid setpoint
Leaving chilled liquid control range
Maximum remote temperature reset
150
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in
Table 23 on page 150.
Mode
Low limit
40.0°F
Water cooling
4.4°C
15.0°F
Glycol cooling
-9.4°C
1.5°F
0.8°C
2°F
1°C
Form 201.28-NM1.1
Issue date: 08/06/2021
High limit
Default
60.0°F
44.0°F
15.6°C
6.7°C
70.0°F
44.0°F
15.6°C
6.7°C
2.5°F
2.0°F
1.4°C
1.1°C
40°F
20°F
22°C
11°C
JOHNSON CONTROLS