Table 24 - Setpoint Limits - York YVAA Installation, Operation & Maintenance Instructions Manual

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 8 - MICROPANEL
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.

TABLE 24 - SETPOINT LIMITS

PROGRAM VALUE
Leaving Chilled Liquid Setpoint
Leaving Chilled Liquid Control Range
Max. Remote Temperature Reset
146
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in
Table 24 on page 146.
MODE
LOW LIMIT
40.0°F
Water Cooling
4.4°C
15.0°F
Glycol Cooling
-9.4°C
1.5°F
-
0.8°C
2°F
-
1°C
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
HIGH LIMIT
DEFAULT
60.0°F
44.0°F
15.6°C
6.7°C
70.0°F
44.0°F
15.6°C
6.7°C
2.5°F
2.0°F
1.4°C
1.1°C
40°F
20°F
22°C
11°C