Table 41 - Setpoint Limits - York YCIV0157 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

Form 201.23-NM2
Issue date: 12/19/2023
The values displayed under each of the key presses
may be changed by keying in new values and pressing
the  (ENTER) key to store the new value into mem-
ory. Where more than one value may be keyed in on a
display, a portion of the data that does not need updat-
ing may be skipped by pressing the  (ENTER) key.
The  (ENTER) key must also be pressed after the
last value in the display to store the data into memory.

Table 41 - Setpoint limits

Program Value
Leaving Chilled Liquid Setpoint
Leaving Chilled Liquid Control Range
Max. Remote Temperature Reset
Johnson Controls
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.
The minimum, maximum, and default values allowed
under the SETPOINTS key are provided in Table 41
on page 263.
Mode
Low Limit
40.0°F
Water Cooling
4.4°C
15.0°F
Glycol Cooling
-9.4°C
1.5°F
-
0.8°C
2°F
-
1°C
Section 8 - Micropanel
High Limit
Default
60.0°F
44.0°F
15.6°C
6.7°C
70.0°F
44.0°F
15.6°C
6.7°C
2.5°F
2.0°F
1.4°C
1.1°C
40°F
20°F
22°C
11°C
8
263