Table 24 - Setpoint Limits - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 8 - MICROPANEL
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.

Table 24 - Setpoint limits

Program value
Leaving chilled liquid setpoint
Leaving chilled liquid control range
Maximum remote temperature reset
138
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in
Table 24 on page 138.
Mode
Low limit
40.0°F
Water cooling
4.4°C
15.0°F
Glycol cooling
-9.4°C
1.5°F
0.8°C
2°F
1°C
Form 201.47-ICOM1
Issue date: 17/11/2022
High limit
Default
60.0°F
44.0°F
15.6°C
6.7°C
70.0°F
44.0°F
15.6°C
6.7°C
2.5°F
2.0°F
1.4°C
1.1°C
40°F
20°F
22°C
11°C
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents