SECTION 8 - MICROPANEL
Options key operation
The OPTIONS key provides the user with a display of
unit configuration and the capability to modify the con-
figuration. These options can only be viewed under the
OPTIONS key. To view the current options settings,
press the OPTIONS key. Each press of the OPTIONS
key or press of the ▲ or ▼ (ARROW) keys will scroll
to the next option setting. The ◄ and ► (ARROW)
keys allow changing the option choices. The  (EN-
TER) key must be pressed after a selection is made to
save the change in memory.
An explanation of each option message is provided.
Display language selection
The display language can be selected for English, Ital-
ian, Polish, Hungarian, German, French, Portuguese,
and Spanish.
OPTIONS
DISPLAY LANGUAGE
◄ ►
XXXXXXXXXXXXXXXXXX
The default language will be English.
154

Options key

Local/remote control mode selection
Local or Remote Control Mode allows the user to se-
lect the chilled liquid temperature control mode.
OPTIONS
◄ ►
When LOCAL CONTROL mode is selected, chilled
liquid control is from the keypad of the chiller. In local
mode, a remote device can read system data, but not
reset operating parameters.
OPTIONS
◄ ►
When REMOTE CONTROL mode is selected, control
of the chilled liquid setpoint is from a remote device
such as an ISN/BAS controller.
OPTIONS
◄ ►
The default mode will be LOCAL CONTROL.
Form 201.28-NM1.1
Issue date: 08/06/2021
Options key
LD10605
LOCAL / REMOTE CONTROL MODE
XXXXXXXXXXXXXXXXXX
LOCAL / REMOTE CONTROL MODE
LOCAL CONTROL
LOCAL / REMOTE CONTROL MODE
REMOTE CONTROL